Inim enea ed300 analog addressable fire detector
Order by
and your product will be shipped
In Stock: 2/PZ
ED300
Smoke and temperature detector
The detector combines smoke and temperature detection to provide (depending on the mode of use) exceptional sensitivity capable of detecting any type of outbreak (critical outbreaks such as flammable liquid fires with little smoke emission) or a very high false alarm rejection.
The operating mode can be set directly from the control unit by choosing from the following:
- “PLUS” mode (factory reset): the detector signals the alarm if the smoke threshold is exceeded (settable as for ED100) or if the temperature threshold is exceeded (settable as for ED200), furthermore in If the temperature rises, the sensitivity of the smoke detection is raised to the maximum. This operating mode, characterized by very high sensitivity, allows you to detect even the most critical fire outbreaks (e.g. combustion of alcohol or similar liquids).
- “OR” mode: the detector signals the alarm if the smoke threshold is exceeded (settable as for ED100) or if the temperature threshold is exceeded (settable as for ED200). This operating mode, characterized by a fair sensitivity, allows the detection of both outbreaks with smoke emission and little heat (e.g. smoldering outbreaks) and outbreaks with little smoke emission and high heat generation (e.g. fire of chemical substances).
- “AND” mode: the detector signals the alarm only if both smoke and temperature thresholds are exceeded at the same time (can be set as for ED100 and ED200). This operating mode, characterized by low sensitivity, allows the incidence of false alarms to be reduced to a minimum. Given the low reactivity of this operating mode, the conditions must be carefully evaluated before using it.
- “SMOKE” mode: the detector behaves like an ED100.
- “TEMPERATURE” mode: the detector behaves like an ED200.
Parameter | ED100 | ED200 | ED300 |
Supply voltage | 19-30 Vdc | ||
Absorption at rest | 200 uA | ||
Absorption in alarm | Max 10 mA | ||
Sensitivity | 0.08 – 0.10 – 0.12 – 0.15 dB/m | A1R (58°C + RoR) – B (72°C) – BR(72°C + RoR) – A2S (58°C) | 0.08 – 0.10 – 0.12 – 0.15 dB/m ---------------------------------------- A1R (58°C + RoR) – B (72°C) – BR(72°C + RoR) – A2S (58°C) ----------------------------------------- AND –OR – PLUS mode |
Operating temperature | -5°C + 40°C | ||
Height (base included) | 46mm | 54mm | |
Diameter | 110mm | ||
Weight (base included) | 160g | ||
Weight (excluding base) | 90g |